Aug 28, 2016  G2A Black Friday Sale IS A PERFECTLY BALANCED SYSTEM WITH NO EXPLOITS - Loot Box IS BROKEN - Duration: 16:10. The Spiffing Brit Recommended for you. The Nexus Mod Manager (NMM) is a free and open source piece of software that allows you to download, install, update and manage your files through an easy to use interface.

Advertising

DN-6999:C • 10/06/2010 — Page 3 of 4

NDM-100(A) Dual Monitor Module

The NDM-100(A) Dual Monitor Module is intended for use in

intelligent, two-wire systems. It provides two independent two-

wire initiating device circuits (IDCs) at two separate, consecutive

addresses. It is capable of monitoring normally open contact fire

alarm and supervisory devices. The module has a single panel-

controlled LED.
NOTE: The NDM-100(A) provides two Style B (Class B) IDC cir-
cuits ONLY. Style D (Class A) IDC circuits are NOT supported in
any application.

NDM-100(A) SPECIFICATIONS

Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 μA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 μA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5' (11.43 cm) high x 4' (10.16 cm) wide x

2.125' (5.398 cm) deep.

NDM-100(A) AUTOMATIC ADDRESSING

The NDM-100(A) automatically assigns itself to two address-

able points, starting with the original address. For example, if

the NDM-100(A) is set to address “26”, then it will automati-

cally assign itself to addresses “26” and “27”.

NOTE: “Ones” addresses on the NDM-100(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.

Installation

NMM-100(A), NZM-100(A), and NDM-100(A) modules mount

directly to a standard 4' (10.16 cm) square, 2.125' (5.398 cm)

deep, electrical box. They may also be mounted to the

SMB500 surface-mount box. Mounting hardware and installa-

tion instructions are provided with each module. All wiring

must conform to applicable local codes, ordinances, and regu-

lations. These modules are intended for power-limited wiring

View and Download Vista Quantum Plus installation and user manual online. H.264 including FSK telemetry. Quantum Plus DVR pdf manual download. Also for: Quantum plus qp04-xxxhf, Quantum plus qp08-xxxhf, Quantum plus qp16-xxxhf. Vista quantum digital video recorder user manual pdf.

only.
The NMM-100P(A) module is intended to be wired and

mounted without rigid connections inside a standard electrical

box. All wiring must conform to applicable local codes, ordi-

nances, and regulations.

Agency Listings and Approvals

In some cases, certain modules may not be listed by certain

approval agencies, or listing may be in process. Consult fac-

tory for latest listing status.

UL: S635

ULC: S635

• FM Approved

CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-

100); 7300-0028:0237 (NDM-100)

MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100);

227-03-E Vol. 3 (NDM-100)

Product Line Information

NOTE: “A” suffix indicates ULC-listed model.

NMM-100(A): Monitor module.
NMM-100P(A): Monitor module, miniature.
NZM-100(A): Monitor module, two-wire detectors.
NDM-100(A): Monitor module, dual, two independent Class B

circuits.
SMB500: Optional surface-mount backbox.

NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 52304.

!

CAUTION:
Avoid duplicating addresses on the system.

Advertising
This manual is related to the following products:
Popular Brands
Popular manuals
Advertising

Page 2 of 4 — DN-6999:C • 10/06/2010

NMM-100P(A) Mini Monitor Module

• Built-in type identification automatically identifies this device

as a monitor module to the panel.

• Powered directly by two-wire SLC loop. No additional power

required.

• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct Decade entry of address: 01 – 99 on FireWarden-

100-2, 01 – 50 on FireWarden-50.

The NMM-100P(A) Mini Monitor Module can be installed in a

single-gang junction directly behind the monitored unit. Its

small size and light weight allow it to be installed without rigid

mounting. The NMM-100P(A) is intended for use in intelligent,

two-wire systems where the individual address of each module

is selected using rotary switches. It provides a two-wire initiat-

ing device circuit for normally-open-contact fire alarm and

security devices. NMM-100P(A)

Ipad Manual Download

NMM-100P(A) APPLICATIONS

Use to monitor a single device or a zone of four-wire smoke

detectors, manual fire alarm pull stations, waterflow devices, or

other normally-open dry-contact devices. May also be used to

monitor normally-open supervisory devices with special super-

Nmm Download Fallout 4

visory indication at the control panel. Monitored circuit/device

is wired as an NFPA Style B (Class B) Initiating Device Circuit.

A 47K ohm End-of-Line Resistor (provided) terminates the cir-

cuit.

NMM-100P(A) OPERATION

Each NMM-100P(A) uses one of the available module

addresses on an SLC loop. It responds to regular polls from

the control panel and reports its type and the status (open/nor-

mal/short) of its Initiating Device Circuit (IDC).

NMM-100P(A) SPECIFICATIONS

Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every

5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC

Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 μA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.

Dimensions: 1.3' (3.302 cm) high x 2.75' (6.985 cm) wide x

0.65' (1.651 cm) deep.
Wire length: 6' (15.24 cm) minimum.

NZM-100(A) Interface Module

• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power

source.

• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct Decade entry of address:, 01 – 99 on FireWarden-

100-2, 01 – 50 on FireWarden-50.

• LED flashes during normal operation.
• LED latches steady to indicate alarm on command from

control panel.

The NZM-100(A) Interface Module is intended for use in intelli-

gent, addressable systems, where the individual address of

each module is selected using built-in rotary switches. This

Manual Download Free

module allows intelligent panels to interface and monitor two-

wire conventional smoke detectors. It transmits the status (nor-

mal, open, or alarm) of one full zone of conventional detectors

back to the control panel. All two-wire detectors being moni-

tored must be UL compatible with the module.

NZM-100(A) APPLICATIONS

Use the NZM-100(A) to monitor a zone of two-wire smoke

detectors. The monitored circuit may be wired as an NFPA

Style B (Class B) or Style D (Class A) Initiating Device Circuit.

A 3.9 K ohm End-of-Line Resistor (provided) terminates the

end of the Style B or D (class B or A) circuit (maximum IDC

Nmm Frost Manual Download Free

loop resistance is 25 ohms). Install ELR across terminals 8

and 9 for Style D application.

NZM-100(A) OPERATION

Each NZM-100(A) uses one of the available module

addresses on an SLC loop. It responds to regular polls from

the control panel and reports its type and the status (open/nor-

mal/short) of its Initiating Device Circuit (IDC). A flashing LED

indicates that the module is in communication with the control

Nmm Mod Manager Download

panel. The LED latches steady on alarm (subject to current

limitations on the loop).

NZM-100(A) SPECIFICATIONS

Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 μA, 1 communication and 1

LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):

DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms

maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5' (11.43 cm) high x 4' (10.16 cm) wide x

1.25' (3.175 cm) deep. Mounts to a 4' (10.16 cm) square x

2.125' (5.398 cm) deep box.